Switchgear and Protection MCQs 2026

80 questions with detailed answers · 54 from past papers · 8 quiz batches available

📚 Electrical Engineering📄 54 Past-Paper Qs✓ Free · No Login Needed
🎯 Mock Test

Read each question, think about the answer, then click Show Answer to reveal the correct option and explanation. Load 10 at a time so it stays manageable — perfect for one-topic study sessions on the bus or during a break.

Page 1 of 1Questions 1–10 of 80
  1. Q1Past Paper · PPSC/FPSC/NTSeasy

    Fuse protects against

    1. Aboth overload and short circuit within its rating
    2. Bonly voltage regulation of line
    3. Conly Ferranti effect
    4. Donly motor synchronizing only
    💡 Explanation:

    Fuses respond to excessive current from overload or fault.

  2. Q2Past Paper · PPSC/FPSC/NTSeasy

    Instantaneous overcurrent element in a relay operates

    1. Aonly after 2 seconds always
    2. Bonly on reverse power
    3. Cwithout intentional time delay once current exceeds setting
    4. Donly when voltage is maximum
    💡 Explanation:

    Instantaneous units trip immediately when fault current exceeds threshold.

  3. Q3Past Paper · PPSC/FPSC/NTSmedium

    Directional overcurrent relay requires

    1. Aonly CT without PT
    2. Bonly fuse melting curve
    3. Cboth current and voltage inputs to determine power flow direction
    4. Donly Buchholz gas pressure
    💡 Explanation:

    Directionality compares current angle relative to voltage reference.

  4. Q4Past Paper · PPSC/FPSC/NTSmedium

    Differential protection compares

    1. Aonly voltage magnitude at one bus
    2. Bonly frequency deviation only
    3. Conly rotor speed of motor
    4. Dcurrent entering and leaving the protected zone
    💡 Explanation:

    Internal faults produce current imbalance detected by differential relay.

  5. Q5Past Paper · PPSC/FPSC/NTSeasy

    Buchholz relay is installed on transformers to detect

    1. Aoverflux due to high voltage only
    2. Bdifferential current only on lines
    3. Cdistance to fault on cable
    4. Dincipient faults producing gas in the oil
    💡 Explanation:

    Gas accumulation and oil surge indicate internal transformer faults.

  6. Q6hard

    Restricted earth fault (REF) protection is sensitive to

    1. Aphase faults on long transmission lines only
    2. Bearth faults within the transformer differential zone near the star point
    3. Cmotor starting inrush only
    4. DFerranti effect only
    💡 Explanation:

    REF uses CT and high-impedance relay for internal earth faults.

  7. Q7Past Paper · PPSC/FPSC/NTSmedium

    Distance relay measures apparent impedance to fault as

    1. AV/I seen by the relay
    2. Bonly current magnitude without voltage
    3. Conly frequency
    4. Donly zero-sequence voltage only
    💡 Explanation:

    Impedance relay infers fault location from measured V and I.

  8. Q8Past Paper · PPSC/FPSC/NTSmedium

    Plug setting multiplier (PSM) equals

    1. Atime setting only
    2. BCT ratio only
    3. Cbreaking capacity only
    4. Dfault current divided by relay pick-up current
    💡 Explanation:

    PSM determines operating point on IDMT curve.

  9. Q9Past Paper · PPSC/FPSC/NTSmedium

    Time setting multiplier (TSM) on an IDMT relay adjusts

    1. ACT primary turns only
    2. Bthe time dial to shift the inverse time curve
    3. Ccircuit breaker arc voltage only
    4. Dmotor slip only
    💡 Explanation:

    TSM selects desired grading with upstream/downstream relays.

  10. Q10Past Paper · PPSC/FPSC/NTSeasy

    Relay coordination on radial feeders ensures

    1. Aall relays trip simultaneously always
    2. Bonly backup relay ever operates
    3. Cthe relay nearest the fault operates first
    4. Dfuse never blows
    💡 Explanation:

    Time and current grading achieve selectivity.

  11. Q11easy

    Numerical protection relays offer

    1. Aonly mechanical induction disc operation
    2. Bprogrammable logic, self-test and event recording
    3. Cno communication capability ever
    4. Dmandatory oil immersion
    💡 Explanation:

    Microprocessor relays integrate multiple functions and communication.

  12. Q12medium

    Electromechanical induction disc relay operating time depends on

    1. Aonly ambient temperature without current
    2. Bonly line length in km
    3. Conly SIL of line
    4. Dcurrent magnitude and time dial setting
    💡 Explanation:

    Disc torque proportional to I² drives the inverse-time characteristic.

  13. Q13Past Paper · PPSC/FPSC/NTSmedium

    CT burden on relay must be kept within rating to avoid

    1. Aincrease of SIL
    2. BFerranti voltage rise
    3. Csaturation and loss of accuracy in protection
    4. Dmotor pull-out torque change
    💡 Explanation:

    Excessive burden causes CT saturation and relay maloperation.

  14. Q14hard

    Overflux protection on transformers responds to

    1. Aonly differential current magnitude
    2. Bonly distance to fault
    3. Conly negative-sequence current only on lines
    4. DV/f ratio exceeding allowable limit
    💡 Explanation:

    High V/f causes transformer core overheating.

  15. Q15medium

    High-set instantaneous element is used to

    1. Areplace all time-delayed elements always
    2. Baccelerate clearance of close-in high-current faults
    3. Cmeasure power factor only
    4. Dcontrol excitation of alternator only
    💡 Explanation:

    High-set units bypass delay for severe nearby faults.

  16. Q16Past Paper · PPSC/FPSC/NTShard

    Stability of differential relay during external faults requires

    1. Aopening of all circuit breakers
    2. BCTs of adequate ratio and knee-point to avoid false differential current
    3. Czero load current always
    4. Dleading power factor at receiving end only
    💡 Explanation:

    Matching CT performance prevents maloperation on through faults.

  17. Q17Past Paper · PPSC/FPSC/NTSeasy

    SF6 circuit breaker uses sulfur hexafluoride primarily because

    1. Ait has high dielectric strength and excellent arc quenching capability
    2. Bit is lighter than air only without arc benefit
    3. Cit eliminates all fault current instantly without arc
    4. Dit replaces the need for contacts
    💡 Explanation:

    SF6 gas cools and de-ionizes the arc efficiently at high pressure.

  18. Q18Past Paper · PPSC/FPSC/NTSeasy

    Vacuum circuit breaker extinguishes arc by

    1. Arapid dielectric recovery in high vacuum between contacts
    2. Boil spray on contacts only
    3. Ccompressed air blast only
    4. Dlong arc running in open air only
    💡 Explanation:

    Vacuum has no ionizable medium, aiding fast arc extinction.

  19. Q19medium

    Air blast circuit breaker interrupts current by

    1. ASF6 liquefaction only
    2. Bvacuum pumping only
    3. Chigh-pressure air jet axially along the arc
    4. Doil decomposition only
    💡 Explanation:

    Compressed air cools and stretches the arc in air-blast designs.

  20. Q20Past Paper · PPSC/FPSC/NTSmedium

    Oil circuit breaker relies on

    1. Avacuum alone without oil
    2. Barc decomposition of oil generating gas flow to extinguish arc
    3. Cpure SF6 without tank
    4. Dno arc interruption medium
    💡 Explanation:

    Oil CBs use oil as arc quenching and insulation medium.

  21. Q21Past Paper · PPSC/FPSC/NTShard

    Making capacity of a circuit breaker refers to

    1. Aonly load current at unity pf
    2. Bmaximum peak current it can close onto without excessive damage
    3. Conly charging current of line only
    4. Donly excitation current of alternator
    💡 Explanation:

    Making capacity relates to peak asymmetrical short-circuit closing duty.

  22. Q22Past Paper · PPSC/FPSC/NTSeasy

    Breaking capacity of a circuit breaker must

    1. Aequal only full-load current
    2. Bbe less than load current always
    3. Cexceed prospective fault level at the installation point
    4. Dignore short-circuit MVA always
    💡 Explanation:

    CB must safely interrupt maximum available fault current.

  23. Q23hard

    Restriking voltage after current zero is the transient voltage appearing

    1. Aonly at transformer no-load
    2. Bonly during motor starting
    3. Cacross breaker contacts during interruption
    4. Donly on DC systems without arc
    💡 Explanation:

    Recovery voltage stress determines successful interruption.

  24. Q24hard

    Rate of rise of restriking voltage (RRRV) affects

    1. Asuccessful arc extinction in oil and air break CBs
    2. Bonly cable charging current magnitude
    3. Conly PID integral gain
    4. Donly Buchholz gas volume only
    💡 Explanation:

    If RRRV exceeds dielectric recovery, restrike occurs.

  25. Q25hard

    Current chopping in vacuum CB on low inductive current can cause

    1. Ahigh transient overvoltages due to rapid current interruption
    2. Breduced insulation stress always
    3. Czero restriking voltage always
    4. Dautomatic reclosing failure only on fuses
    💡 Explanation:

    Sudden energy release in inductive circuits produces overvoltages.

  26. Q26Past Paper · PPSC/FPSC/NTSmedium

    Auto-reclosing on transmission lines attempts

    1. Anever used on overhead lines
    2. Bonly on underground cables always without blocking
    3. Cautomatic closure after brief outage to restore permanent faults selectively
    4. Dreplacement of all relays
    💡 Explanation:

    Reclosing improves supply continuity for transient faults like lightning.

  27. Q27medium

    Arc chutes in air break low-voltage breakers

    1. Aincrease fault level
    2. Blengthen and cool the arc for extinction
    3. Creplace CT cores
    4. Dmeasure distance to fault
    💡 Explanation:

    Splitters and chutes improve dielectric recovery in air.

  28. Q28medium

    Minimum oil circuit breaker (MOCB) differs from bulk oil CB by

    1. Ausing smaller quantity of oil in interrupting chamber only
    2. Busing no oil at all
    3. Coperating only at EHV
    4. Dhaving no moving contacts
    💡 Explanation:

    MOCB reduces oil quantity compared to bulk-oil designs.

  29. Q29Past Paper · PPSC/FPSC/NTSmedium

    SF6 breaker contact separation is accompanied by

    1. Ahigh-pressure gas blast through the arc region
    2. Bonly vacuum creation in main tank
    3. Conly oil jet without gas
    4. Donly fuse wire melting
    💡 Explanation:

    Puffer or blast designs force SF6 through the arc column.

  30. Q30Past Paper · PPSC/FPSC/NTSeasy

    Circuit breaker rated voltage must match

    1. Aonly load current in amperes
    2. Bonly motor slip
    3. Conly cable length in metres only
    4. Dhighest system voltage including insulation coordination margins
    💡 Explanation:

    Voltage rating ensures insulation withstand under normal and transient conditions.

  31. Q31easy

    Operating mechanism of a CB may be

    1. Aonly manual fuse wire replacement
    2. Bspring charged, pneumatic or hydraulic depending on design
    3. Conly permanent magnet only without motion
    4. Donly Buchholz float movement
    💡 Explanation:

    Stored-energy mechanisms provide fast and reliable operation.

  32. Q32Past Paper · PPSC/FPSC/NTSmedium

    Successful interruption requires current to reach

    1. Amaximum peak always without zero
    2. Bnatural or forced zero with adequate dielectric recovery across contacts
    3. CDC offset only without decay
    4. Dinfinite frequency always
    💡 Explanation:

    Alternating current must pass through zero for AC interruption.

  33. Q33Past Paper · PPSC/FPSC/NTSeasy

    HRC fuse stands for

    1. Ahigh reactive compensation
    2. Bhigh rupturing capacity fuse
    3. Chigh resistance conductor
    4. Dhigh relay coordination only
    💡 Explanation:

    HRC fuses safely interrupt high fault currents within rated capacity.

  34. Q34Past Paper · PPSC/FPSC/NTSeasy

    Cartridge type HRC fuse contains

    1. Aonly rewirable wire in open air
    2. Bonly oil without element
    3. Conly vacuum interrupter
    4. Dsilver or copper element enclosed in silica sand filled tube
    💡 Explanation:

    Sand quenches arc and limits peak let-through current.

  35. Q35Past Paper · PPSC/FPSC/NTSmedium

    Cut-off current of a current-limiting fuse is

    1. Amaximum instantaneous current reached before fuse clears
    2. Bsteady-state load current only
    3. Ctransformer magnetizing current only
    4. Dmotor full-load current only
    💡 Explanation:

    Fast melting limits prospective peak fault current.

  36. Q36Past Paper · PPSC/FPSC/NTSeasy

    Inverse time characteristic of a fuse means

    1. Atime fixed for all currents
    2. Bfuse never blows on overload
    3. Cblow time increases with fault current
    4. Dhigher overcurrent clears in shorter time
    💡 Explanation:

    Fuse time-current curve is inverse like many overcurrent relays.

  37. Q37Past Paper · PPSC/FPSC/NTSeasy

    Rewirable Kit-Kat fuse is considered obsolete because

    1. Ait has highest rupturing capacity
    2. Bit has lower breaking capacity and poor discrimination
    3. Cit is used on 400 kV lines
    4. Dit replaces numerical relays
    💡 Explanation:

    Open rewirable fuses are unsafe for modern fault levels.

  38. Q38medium

    Expulsion fuse used in outdoor distribution

    1. Auses arc energy to expel gases that extinguish the arc
    2. Brequires SF6 tank always
    3. Coperates only on DC
    4. Dcannot be used outdoors
    💡 Explanation:

    Expulsion action blows arc products out of the tube.

  39. Q39Past Paper · PPSC/FPSC/NTSmedium

    Fuse coordination ensures

    1. Aall fuses blow together always
    2. Bbreaker never operates
    3. Crelay never picks up
    4. Dfault is cleared by the smallest protective device upstream of the fault
    💡 Explanation:

    Selectivity minimizes outage area.

  40. Q40Past Paper · PPSC/FPSC/NTSmedium

    Current-limiting fuse reduces

    1. Aline SIL to zero
    2. Bexcitation reactance of alternator
    3. CBode gain margin only
    4. DI²t let-through energy seen by downstream equipment
    💡 Explanation:

    Limiting peak current protects cables and switchgear from thermal/mechanical stress.

  41. Q41Past Paper · PPSC/FPSC/NTSeasy

    Fuse rating in amperes indicates

    1. Amaximum current the fuse can carry continuously without melting
    2. Bminimum fault MVA only
    3. Cdistance relay reach only
    4. DPID proportional gain only
    💡 Explanation:

    Rated current must exceed normal load but clear on overcurrent.

  42. Q42Past Paper · PPSC/FPSC/NTSeasy

    Unlike a circuit breaker, a fuse

    1. Amust be replaced after one fault operation
    2. Bcan reclose automatically always without inspection
    3. Cmeasures impedance to fault
    4. Dprovides differential protection alone
    💡 Explanation:

    Fuses are single-shot protective devices.

  43. Q43Past Paper · PPSC/FPSC/NTSmedium

    Drop-out fuse cutout on distribution poles allows

    1. Avisible open isolation when fuse carrier drops after operation
    2. Bmeasurement of positive-sequence impedance only
    3. Cautomatic PID tuning
    4. Ddistance protection zone extension
    💡 Explanation:

    Drop-out action indicates blown fuse and isolates section.

  44. Q44hard

    Striker fuse operates an indicator or tripping mechanism by

    1. Ameasuring V/f on transformer only
    2. Bcomputing symmetrical components only
    3. Cgenerating PWM for inverter only
    4. Dmechanical movement when fuse element blows
    💡 Explanation:

    Striker pin provides remote indication or latch release.

  45. Q45medium

    Selectivity between series fuses requires

    1. Aidentical ratings always
    2. Bdownstream fuse always slower
    3. Cno coordination study
    4. Dupstream fuse has higher rating or slower characteristic than downstream
    💡 Explanation:

    Time-current grading achieves fuse selectivity.

  46. Q46hard

    Phase-a to ground voltage during SLG fault is

    1. Aalways equal for all phases
    2. Balways maximum on faulted phase only without ground
    3. Capproximately zero at fault location while other phases remain finite
    4. Dundefined without sequence networks
    💡 Explanation:

    Faulted phase voltage collapses near fault; others may rise on ungrounded systems.

  47. Q47Past Paper · PPSC/FPSC/NTSeasy

    IDMT overcurrent relay characteristic means

    1. Aoperating time decreases as fault current increases above pick-up
    2. Btime is fixed regardless of current
    3. Crelay never operates on overload
    4. Dpick-up is independent of plug setting
    💡 Explanation:

    Inverse definite minimum time relays give faster tripping for higher fault currents.

  48. Q48Past Paper · PPSC/FPSC/NTSmedium

    Sand filling in HRC fuse cartridge helps

    1. Aincrease fault current magnitude
    2. Bquench the arc and absorb energy during interruption
    3. Creduce breaking capacity
    4. Deliminate the need for element
    💡 Explanation:

    Sand fuses and cools arc products rapidly.

  49. Q49medium

    Fuse element material is often silver because

    1. Ait never melts
    2. Bit increases fault level
    3. Cit has stable melting characteristics and good conductivity
    4. Dit replaces CT saturation curve
    💡 Explanation:

    Silver provides predictable time-current behaviour.

  50. Q50Past Paper · PPSC/FPSC/NTSeasy

    Fortescue theorem states that

    1. Aany unbalanced three-phase phasors can be resolved into three balanced sets
    2. Bonly positive sequence exists always
    3. Czero sequence requires no ground path
    4. Dnegative sequence rotates same as positive
    💡 Explanation:

    Positive, negative and zero sequence components sum to the original unbalanced system.

  51. Q51Past Paper · PPSC/FPSC/NTSeasy

    Positive sequence network is used for

    1. Aonly double line-to-ground faults without line
    2. Bonly DC circuits
    3. Conly single-phase motors without neutral
    4. Dbalanced three-phase faults and normal balanced operation
    💡 Explanation:

    Balanced conditions involve only positive sequence.

  52. Q52Past Paper · PPSC/FPSC/NTSmedium

    Negative sequence components produce

    1. Areverse rotating field harmful to rotating machines
    2. Bno effect on induction motors
    3. Conly DC offset in transformers
    4. Donly Ferranti voltage rise
    💡 Explanation:

    Negative sequence causes heating and torque pulsations in machines.

  53. Q53Past Paper · PPSC/FPSC/NTSmedium

    Zero sequence current flows only when

    1. Asystem is perfectly balanced always
    2. Bdelta winding carries zero sequence freely always
    3. Cno ground exists anywhere
    4. Da return path exists for the zero sequence network (usually ground/neutral)
    💡 Explanation:

    Zero sequence requires grounded neutral or earth return.

  54. Q54Past Paper · PPSC/FPSC/NTSmedium

    Delta-connected transformer winding blocks

    1. Apositive sequence only
    2. Bzero sequence current from passing through the delta
    3. Call sequence networks equally
    4. Dnegative sequence only always on all designs
    💡 Explanation:

    Delta provides no zero-sequence path through the winding.

  55. Q55Past Paper · PPSC/FPSC/NTSeasy

    Single line-to-ground (SLG) fault involves

    1. Aonly positive sequence alone
    2. Ball three sequence networks connected in series at fault point
    3. Conly negative sequence alone
    4. Dno zero sequence ever
    💡 Explanation:

    SLG is the most common fault and uses all sequence networks.

  56. Q56Past Paper · PPSC/FPSC/NTSmedium

    Line-to-line (LL) fault involves

    1. Azero sequence only
    2. Bpositive sequence only
    3. Cpositive and negative sequence networks in series
    4. Dno sequence analysis needed
    💡 Explanation:

    LL faults have no zero-sequence component without ground involvement.

  57. Q57Past Paper · PPSC/FPSC/NTShard

    Sequence impedances Z1, Z2, Z0 of a static line typically satisfy

    1. AZ0 = 0 always
    2. BZ1 = Z2 and Z0 > Z1 for overhead lines with ground return
    3. CZ1 = Z0 always without ground wires
    4. DZ2 = infinity always
    💡 Explanation:

    Mutual coupling to ground makes zero-sequence impedance larger.

  58. Q58Past Paper · PPSC/FPSC/NTSmedium

    Unbalanced fault analysis using symmetrical components requires

    1. Aonly per unit change of base
    2. Bonly Bode plot of open-loop system
    3. Conly SCR latching current test only
    4. Dinterconnection of sequence networks according to fault type
    💡 Explanation:

    Fault boundary conditions determine series/parallel sequence connections.

  59. Q59hard

    Negative sequence heating in synchronous machines is severe because

    1. Ano current flows in rotor
    2. Bonly stator heats without rotor effect
    3. Crotor sees double-frequency induced currents relative to forward field
    4. Dmachine runs as induction generator only
    💡 Explanation:

    Negative sequence creates reverse rotating field and rotor heating.

  60. Q60hard

    Conversion from abc phase quantities to symmetrical components uses

    1. Aonly Laplace transform of DC signal
    2. Bonly Fourier series of square wave without phase
    3. Conly PID derivative term
    4. Dlinear transformation with operator a = e^(j120°)
    💡 Explanation:

    Fortescue transformation matrix combines a operators.

  61. Q61Past Paper · PPSC/FPSC/NTSmedium

    Double line-to-ground (LLG) fault uses

    1. Apositive sequence only
    2. Bno zero sequence if ungrounded system only in some cases
    3. CDC component only
    4. Dpositive, negative and zero sequence networks interconnected
    💡 Explanation:

    LLG faults generally involve all three sequences on grounded systems.

  62. Q62Past Paper · PPSC/FPSC/NTSeasy

    Balanced three-phase load carries

    1. Aequal negative and zero sequence always
    2. Bonly positive sequence current under normal conditions
    3. Conly zero sequence
    4. Dunbalanced sequence always
    💡 Explanation:

    Symmetry implies absence of negative and zero sequence.

  63. Q63Past Paper · PPSC/FPSC/NTSmedium

    Grounding system design affects primarily

    1. Azero sequence impedance and fault current magnitude for earth faults
    2. Bonly positive sequence only on delta systems without ground
    3. Conly motor slip under load
    4. Donly inverter switching frequency only
    💡 Explanation:

    Solid grounding lowers Z0 and increases SLG fault current.

  64. Q64Past Paper · PPSC/FPSC/NTSmedium

    Symmetrical components simplify fault studies because

    1. Athey eliminate the need for per unit
    2. Bthey remove all resistances
    3. Csequence networks are often uncoupled except at fault point
    4. Dthey set all voltages equal
    💡 Explanation:

    Uncoupled sequence networks simplify analysis of unbalanced faults.

  65. Q65Past Paper · PPSC/FPSC/NTSeasy

    Impedance relay measures

    1. Aonly real power flow direction without voltage
    2. Bonly third harmonic only
    3. Conly DC resistance of tower footing only
    4. Dapparent impedance V/I to the fault point
    💡 Explanation:

    Measured impedance compared to reach setting determines trip.

  66. Q66Past Paper · PPSC/FPSC/NTSmedium

    Mho relay characteristic on R-X diagram is

    1. Aa circle passing through origin oriented to forward faults
    2. Ba vertical line only at all settings
    3. Ca horizontal line at negative reactance only always
    4. Dunrelated to impedance plane
    💡 Explanation:

    Mho element is inherently directional toward forward line faults.

  67. Q67Past Paper · PPSC/FPSC/NTSmedium

    Zone 1 distance protection typically covers

    1. Aentire adjacent line without delay always
    2. Bonly transformer winding only
    3. Cabout 80% of protected line length instantaneously
    4. Donly busbar differential zone
    💡 Explanation:

    Zone 1 underreach margin avoids overreach into adjacent equipment.

  68. Q68Past Paper · PPSC/FPSC/NTSmedium

    Zone 2 of distance relay provides

    1. Abackup coverage beyond line end with intentional time delay
    2. Binstantaneous tripping for all faults on adjacent lines without coordination
    3. Conly reverse power protection
    4. Donly REF on transformer
    💡 Explanation:

    Zone 2 reaches remote bus with grading delay.

  69. Q69hard

    Zone 3 distance element acts as

    1. Ainstantaneous primary only without settings
    2. Bfar backup with longest time delay
    3. Cmotor stall protection only
    4. DBuchholz gas detection only
    💡 Explanation:

    Zone 3 covers remote lines/transformers as backup.

  70. Q70Past Paper · PPSC/FPSC/NTShard

    Power swing blocking in distance relays prevents

    1. Aall internal transformer faults
    2. Ball SLG faults always
    3. Cfuse blowing on overload
    4. Dtripping during stable power swings without fault
    💡 Explanation:

    Large impedance swings during stability events must not trip line.

  71. Q71hard

    Carrier aided distance schemes use

    1. Aonly DC injection in rotor
    2. Bonly cable Murray loop only
    3. Ccommunication between line ends for permissive or blocking tripping
    4. Donly PID anti-windup only
    💡 Explanation:

    Pilot channels accelerate tripping for internal faults.

  72. Q72Past Paper · PPSC/FPSC/NTSmedium

    Reach setting of distance relay is specified in

    1. Aonly amperes of full-load current
    2. Bonly motor RPM only
    3. Cohms or percent of line positive-sequence impedance
    4. Donly per unit sag only
    💡 Explanation:

    Reach defines impedance limit seen by relay for zone coverage.

  73. Q73Past Paper · PPSC/FPSC/NTShard

    Fault resistance can cause distance relay to

    1. Aalways overreach without exception
    2. Bignore all faults
    3. Cmeasure only zero sequence
    4. Dunderreach compared to metallic fault assumption
    💡 Explanation:

    Arc and ground resistance add to measured impedance.

  74. Q74hard

    Blinders on distance relays exclude

    1. Ainternal differential current only
    2. Btransformer magnetizing inrush only without harmonic restraint
    3. Cload encroachment into tripping characteristic
    4. DFerranti effect on open end only
    💡 Explanation:

    Blinders prevent tripping on heavy load impedance points.

  75. Q75hard

    Quadrilateral distance characteristic allows

    1. Aonly circular mho without resistance coverage adjustment
    2. Bonly instantaneous overcurrent without voltage
    3. Cindependent control of resistive and reactive reach
    4. Donly fuse time-current curve only
    💡 Explanation:

    Quadrilateral suits long lines and high fault resistance.

  76. Q76hard

    Permissive overreach transfer trip (POTT) uses

    1. Aonly local zone 3 without communication
    2. Bonly Buchholz relay contacts
    3. Creceived permissive signal from remote end to trip on internal fault
    4. Donly open-loop PID step response
    💡 Explanation:

    Communication confirms remote detection before accelerated trip.

  77. Q77Past Paper · PPSC/FPSC/NTSmedium

    Step distance scheme applies

    1. Amultiple impedance zones with increasing time delays
    2. Bsingle instantaneous zone only always
    3. Conly DC machine commutation only
    4. Donly cable capacitance grading only
    💡 Explanation:

    Stepped zones provide primary and backup grading along line.

  78. Q78Past Paper · PPSC/FPSC/NTSeasy

    Distance relay is primarily applied on

    1. Alow-voltage lighting circuits only
    2. Bonly battery rooms without CT
    3. Ctransmission lines and EHV feeders
    4. Donly open-loop water level control only
    💡 Explanation:

    Impedance measurement suits long lines with significant Z.

  79. Q79hard

    Voltage memory in distance relays helps

    1. Aincreasing Ferranti rise
    2. Bmaintaining directional and impedance measurement during close-in faults with voltage collapse
    3. Cmeasuring motor slip only
    4. Dreplacing symmetrical components entirely
    💡 Explanation:

    Stored voltage polarizes relay when fault voltage is depressed.

  80. Q80hard

    Switch-on-to-fault (SOTF) logic in distance protection allows

    1. Ablocking of all zone 1 always
    2. Bfast tripping when breaker closes onto a fault
    3. Cdisabling carrier channel permanently
    4. Dmeasuring only third harmonic in transformer only without restraint
    💡 Explanation:

    SOTF detects fault present at closure without normal delay.