Transformers MCQs 2026
88 questions with detailed answers · 31 from past papers · 9 quiz batches available
Choose a Quiz Batch. Each batch has 10 questions from this topic, in order. Take them one by one to work through all 88 MCQs. Login to save your scores and see your best per batch.
Read each question, think about the answer, then click Show Answer to reveal the correct option and explanation. Load 10 at a time so it stays manageable — perfect for one-topic study sessions on the bus or during a break.
- Q1medium
Parallel operation of Yy0 and Dd0 transformers is
💡 Explanation:Different phase shifts cause large circulating currents even if voltage ratios match.
- Q2hard
Vector group Yd1 indicates phase displacement of
💡 Explanation:Clock number 1 means secondary leads primary by 30° in positive sequence.
- Q3hard
Three-phase transformer vector group Dy11 means
💡 Explanation:Dy11: secondary line voltage leads primary by 30° (clock position 11 = −30° from 12).
- Q4hard
Pulse transformer design emphasizes
💡 Explanation:Signal integrity requires minimal leakage L and distributed capacitance for sharp pulses.
- Q5medium
A welding transformer is designed for
💡 Explanation:High leakage reactance limits short-circuit current and provides stable arc voltage.
- Q6Past Paper · PPSC/FPSC/CSShard
Equivalent resistance referred to secondary equals
💡 Explanation:Primary resistance referred to secondary is scaled by inverse turns ratio squared.
- Q7easy
Copper losses in a transformer vary as
💡 Explanation:Pc = I²R; at x per unit load, Pc = x² × full-load copper loss.
- Q8Past Paper · PPSC/FPSC/CSSeasy
Iron losses in a transformer are
💡 Explanation:Core flux remains near rated value at normal operation, so Pi stays essentially constant.
- Q9easy
Transformers are rated in
💡 Explanation:Rating is apparent power because load power factor is unknown; losses depend on current not PF alone.
- Q10Past Paper · PPSC/FPSC/CSSmedium
Conservator tank on a transformer maintains
💡 Explanation:Oil expands/contracts with temperature; conservator allows breathing without exposing oil to air.
- Q11easy
Silica gel breather in a transformer prevents
💡 Explanation:Silica gel absorbs moisture from air drawn into conservator during oil contraction.
- Q12Past Paper · PPSC/FPSC/CSSeasy
The no-load current of a power transformer is typically
💡 Explanation:Mostly magnetizing component; small compared to rated current in large power transformers.
- Q13medium
Stacking laminations reduces eddy current loss because
💡 Explanation:Thinner laminations confine eddy currents to small loops, reducing I²R eddy loss.
- Q14Past Paper · PPSC/FPSC/CSShard
Eddy current loss in transformer laminations varies approximately with
💡 Explanation:Pe ∝ f² × B² × t² for thin laminations, rising sharply with flux and frequency.
- Q15Past Paper · PPSC/FPSC/CSSeasy
The EMF induced in a transformer primary winding is given by the equation
💡 Explanation:The RMS induced EMF per phase equals 4.44 times frequency, number of turns, and maximum flux in webers.
- Q16Past Paper · PPSC/FPSC/CSSmedium
Maximum flux Φm in a transformer core is directly proportional to
💡 Explanation:From E = 4.44 f N Φm, for fixed N, Φm ∝ V/f, which is why flux must be limited at low frequency.
- Q17easy
The turns ratio of an ideal transformer is defined as
💡 Explanation:Turns ratio a = Np/Ns relates primary and secondary voltages and currents inversely.
- Q18Past Paper · PPSC/FPSC/CSSeasy
For an ideal transformer, if primary has 1000 turns and secondary has 100 turns, the turns ratio is
💡 Explanation:a = Np/Ns = 1000/100 = 10, meaning primary voltage is ten times secondary voltage.
- Q19easy
In an ideal step-down transformer, the secondary current compared to primary current is
💡 Explanation:Power conservation gives VpIp = VsIs, so lower secondary voltage means higher secondary current.
- Q20Past Paper · PPSC/FPSC/CSSeasy
The voltage ratio of an ideal transformer equals
💡 Explanation:Vp/Vs = Np/Ns for an ideal transformer with same flux linking both windings.
- Q21Past Paper · PPSC/FPSC/CSSmedium
Open-circuit (OC) test on a transformer is performed on the
💡 Explanation:OC test uses rated voltage on LV side while HV is open, keeping test voltage safely accessible.
- Q22medium
The open-circuit test of a transformer primarily determines
💡 Explanation:At no load, copper loss is negligible; measured input gives iron loss and magnetizing parameters.
- Q23Past Paper · PPSC/FPSC/CSSmedium
Short-circuit (SC) test on a transformer is normally conducted on the
💡 Explanation:Reduced voltage (5-10% rated) is applied to HV with LV shorted to measure impedance and copper loss.
- Q24medium
The short-circuit test of a transformer is used to determine
💡 Explanation:Rated current flows at reduced voltage; iron loss is small and copper loss dominates.
- Q25Past Paper · PPSC/FPSC/CSSeasy
During OC test, wattmeter reading represents mainly
💡 Explanation:No-load current is small, so copper loss is negligible compared to constant core losses.
- Q26medium
During SC test, the applied voltage is approximately
💡 Explanation:Short-circuit impedance limits current to rated value at a small fraction of rated voltage.
- Q27Past Paper · PPSC/FPSC/CSSmedium
All-day efficiency of a distribution transformer is also called
💡 Explanation:It considers energy losses over 24 hours at varying load cycles, not just one load point.
- Q28easy
An auto-transformer differs from a two-winding transformer because
💡 Explanation:Part of the winding is common, reducing copper and size for same voltage ratio.
- Q29Past Paper · PPSC/FPSC/CSShard
Savings in copper of an auto-transformer compared to two-winding type is approximately
💡 Explanation:Common winding carries only the difference current, saving conductor material.
- Q30medium
Auto-transformers are NOT used when
💡 Explanation:Shared winding provides no electrical isolation between primary and secondary.
- Q31Past Paper · PPSC/FPSC/CSSeasy
An isolation transformer has turns ratio of
💡 Explanation:Isolation transformers typically have equal turns to transfer voltage while isolating circuits.
- Q32easy
Primary purpose of an isolation transformer is to
💡 Explanation:It separates equipment from supply ground, reducing shock hazard and noise coupling.
- Q33Past Paper · PPSC/FPSC/CSSeasy
A current transformer (CT) is connected in
💡 Explanation:CT primary carries line current; secondary feeds measuring instruments with stepped-down current.
- Q34easy
Standard secondary current of most instrument CTs is
💡 Explanation:Industry standardizes on 5 A (or 1 A) secondary for ammeters, relays, and energy meters.
- Q35Past Paper · PPSC/FPSC/CSSeasy
A potential transformer (PT) is connected in
💡 Explanation:PT steps down high voltage to standard 110 V or 100 V for metering and protection.
- Q36Past Paper · PPSC/FPSC/CSSmedium
The secondary of a CT must never be
💡 Explanation:Open secondary with primary energized causes dangerous overvoltage due to magnetizing flux buildup.
- Q37easy
CT ratio 200/5 means secondary current of 5 A when primary carries
💡 Explanation:Ratio expresses primary to secondary current transformation for measurement scaling.
- Q38medium
Per-unit system for transformers uses base quantities such that
💡 Explanation:pu = actual value / base value; bases chosen for convenient calculation on common MVA and kV.
- Q39Past Paper · PPSC/FPSC/CSShard
Base impedance in per-unit system is given by
💡 Explanation:Zbase = V²/S in consistent units (e.g., kV and MVA) for per-unit impedance conversion.
- Q40hard
Transformer per-unit impedance is independent of
💡 Explanation:When properly referred, Zpu is the same whether calculated on HV or LV side.
- Q41medium
Hysteresis loss in transformer core depends on
💡 Explanation:Ph ∝ f × Bmax^n (Steinmetz); hysteresis varies with flux density and frequency.
- Q42easy
Commercial efficiency of a transformer is defined at
💡 Explanation:Commercial efficiency = output at full load / (output + losses at full load), used for rating comparisons.
- Q43Past Paper · PPSC/FPSC/CSSmedium
Maximum efficiency of a transformer occurs when
💡 Explanation:Total loss Pt = Pi + Pc×(x)²; minimum when dPt/dx = 0 gives x = √(Pi/Pc), i.e., Cu loss = iron loss.
- Q44hard
If iron loss is 2 kW and full-load copper loss is 8 kW, load fraction for maximum efficiency is
💡 Explanation:x = √(Pi/Pc) = √(2/8) = √(0.25) = 0.5 or 50% load.
- Q45Past Paper · PPSC/FPSC/CSSeasy
At maximum efficiency, the variable copper loss equals
💡 Explanation:This is the fundamental condition for minimum total loss at a given load fraction.
- Q46medium
A transformer has Pi = 1 kW and Pc = 4 kW. Maximum efficiency occurs at
💡 Explanation:x = √(1/4) = 0.5, so maximum efficiency is at half rated load.
- Q47Past Paper · PPSC/FPSC/CSSmedium
Star-star (Y-Y) connection of three-phase transformers gives
💡 Explanation:Y-Y connection preserves phase sequence with no inherent angular displacement.
- Q48medium
Delta-delta (Δ-Δ) connection is preferred when
💡 Explanation:Open-delta operation allows continued two-phase service at reduced capacity using two transformers.
- Q49Past Paper · PPSC/FPSC/CSSmedium
Star-delta (Y-Δ) connection introduces a phase shift of
💡 Explanation:Y-Δ shifts secondary voltage by 30° relative to primary, important for parallel operation.
- Q50hard
Delta-star (Δ-Y) connection produces a phase shift of
💡 Explanation:Δ-Y is the mirror of Y-Δ; secondary leads primary by 30 electrical degrees.
- Q51Past Paper · PPSC/FPSC/CSSmedium
Scott connection uses two transformers to convert
💡 Explanation:Scott T-connection provides balanced two-phase supply from a three-phase source.
- Q52hard
In Scott connection, one transformer is called teaser and has
💡 Explanation:Teaser transformer winding is tapped at 86.6% (√3/2 × 50%) to obtain 90° displacement.
- Q53Past Paper · PPSC/FPSC/CSSeasy
ONAN cooling classification means
💡 Explanation:ONAN relies on natural oil circulation and natural air cooling without pumps or fans.
- Q54easy
OFAF cooling in transformers stands for
💡 Explanation:OFAF uses oil pumps and forced air fans for higher capacity heat removal.
- Q55Past Paper · PPSC/FPSC/CSSeasy
As transformer load increases, voltage regulation generally
💡 Explanation:Greater load current causes larger resistive and reactive drops, worsening regulation.
- Q56medium
Voltage regulation of a transformer is defined as
💡 Explanation:Regulation measures percentage drop in secondary terminal voltage from no-load to full-load.
- Q57Past Paper · PPSC/FPSC/CSShard
Negative voltage regulation in a transformer can occur when
💡 Explanation:Leading PF can cause voltage rise at terminals, giving negative regulation.
- Q58medium
The approximate equivalent circuit of a transformer is referred to
💡 Explanation:Parameters are referred to one winding for simplified analysis using turns ratio.
- Q59Past Paper · PPSC/FPSC/CSSmedium
In the exact equivalent circuit, R0 and X0 represent
💡 Explanation:Parallel branch R0-X0 accounts for iron loss and magnetizing reactance.
- Q60medium
Series components R1 and X1 in transformer equivalent circuit represent
💡 Explanation:Impedance drop in windings is modeled by series R and X referred to one side.
- Q61Past Paper · PPSC/FPSC/CSSeasy
Buchholz relay is installed in
💡 Explanation:It detects gas accumulation and oil surge from internal faults such as arcing or overheating.
- Q62medium
Buchholz relay operates on the principle of
💡 Explanation:Decomposing oil releases gas; severe faults displace oil, tripping the relay.
- Q63Past Paper · PPSC/FPSC/CSSeasy
A Buchholz relay provides protection against
💡 Explanation:It gives early warning for winding faults, core overheating, and loss of oil before major damage.
- Q64medium
On-load tap changer (OLTC) allows
💡 Explanation:OLTC switches taps under load using resistors or reactor transition to maintain voltage.
- Q65Past Paper · PPSC/FPSC/CSSeasy
Off-load tap changer must be operated when
💡 Explanation:De-energizing prevents arcing and ensures safe tap contact change.
- Q66medium
Leakage flux in a transformer links
💡 Explanation:Leakage flux does not link both windings and causes voltage drop modeled as leakage reactance.
- Q67medium
Percentage impedance of a transformer indicates
💡 Explanation:Z% = (short-circuit voltage / rated voltage) × 100 at rated current.
- Q68medium
Two transformers can operate in parallel if they have
💡 Explanation:Mismatch causes circulating current and unequal load sharing.
- Q69medium
Polarity test of a transformer determines
💡 Explanation:Additive or subtractive polarity affects parallel connection and relay CT connections.
- Q70hard
Subtractive polarity means
💡 Explanation:Terminals 1-H1 and 2-H2 are on same physical side for subtractive marking.
- Q71easy
Three single-phase transformers in bank can replace
💡 Explanation:Banking provides flexibility; one unit can be spare or replaced individually.
- Q72hard
Open-delta connection delivers
💡 Explanation:With one transformer removed, capacity = 1/√3 ≈ 57.7% of complete delta bank rating.
- Q73hard
Tertiary winding in Y-Y-Δ transformer bank is often
💡 Explanation:Delta tertiary provides path for zero-sequence current and stabilizes tertiary flux unbalance.
- Q74hard
Zero-sequence impedance of Y-Δ transformer is
💡 Explanation:Delta blocks zero-sequence current from passing to Y primary, giving high Z0.
- Q75medium
Instrument PT secondary is normally grounded for
💡 Explanation:Grounding prevents dangerous floating potential on metering circuits and provides reference for relays.
- Q76hard
CT accuracy class 5P20 means
💡 Explanation:Protection class CT maintains specified accuracy up to 20× rated primary for fault currents.
- Q77medium
Magnetizing inrush current occurs when transformer is
💡 Explanation:Residual flux plus applied flux can saturate core momentarily, drawing large inrush.
- Q78hard
To reduce switching inrush, transformers may use
💡 Explanation:Point-on-wave switching and pre-insertion resistors limit peak inrush current magnitude.
- Q79medium
Core saturation during inrush causes
💡 Explanation:Saturated core needs high magnetizing MMF, producing harmonic-rich inrush lasting several cycles.
- Q80easy
Distribution transformers use
💡 Explanation:They reduce HV distribution to LV utilization voltage at poles or pads.
- Q81medium
Power transformer impedance is designed mainly for
💡 Explanation:Higher Z% limits short-circuit current but increases voltage regulation trade-off.
- Q82easy
Transformer oil serves as
💡 Explanation:Mineral oil insulates windings and transfers heat from core and coils to tank walls.
- Q83medium
Dissolved gas analysis (DGA) in transformers detects
💡 Explanation:Gases like H2, CH4, C2H2 indicate overheating, partial discharge, or arcing in oil/paper.
- Q84hard
Winding hot-spot temperature limit for oil transformers is typically guided by
💡 Explanation:Hot-spot above 98-110°C accelerates cellulose aging; insulation life halves roughly every 6-7°C rise.
- Q85medium
FR3 or ester oil in transformers offers
💡 Explanation:Natural ester fluids have fire points above 300°C and are environmentally friendlier.
- Q86easy
Transformer tank is earthed to
💡 Explanation:Grounding the tank protects personnel and ensures proper operation of protective devices.
- Q87easy
Lightning arrester on transformer protects against
💡 Explanation:Arresters clamp transient overvoltages from lightning or switching before they damage insulation.
- Q88hard
Surge impedance loading (SIL) relates to
💡 Explanation:While line-related, transformer-line interface design considers SIL for voltage profile on long lines.