High Voltage Engineering MCQs 2026

49 questions with detailed answers · 33 from past papers · 5 quiz batches available

📚 Electrical Engineering📄 33 Past-Paper Qs✓ Free · No Login Needed
🎯 Mock Test

Read each question, think about the answer, then click Show Answer to reveal the correct option and explanation. Load 10 at a time so it stays manageable — perfect for one-topic study sessions on the bus or during a break.

Page 1 of 1Questions 1–10 of 49
  1. Q1Past Paper · PPSC/FPSC/NTShard

    Townsend breakdown mechanism in gases describes

    1. Aavalanche multiplication of electrons leading to ionization breakdown
    2. Bonly liquid dielectric polarization
    3. Conly solid lattice vibration
    4. Donly magnetic saturation
    💡 Explanation:

    Primary ionization and secondary processes (γ) sustain avalanche until breakdown.

  2. Q2Past Paper · PPSC/FPSC/NTSmedium

    Paschen law relates breakdown voltage in uniform field gaps to

    1. Aonly temperature of conductor
    2. Bonly humidity of oil alone
    3. Conly cable length in km
    4. Dproduct of pressure and gap distance (pd)
    💡 Explanation:

    Vb = f(pd) shows minimum breakdown at a particular pd value.

  3. Q3hard

    Streamer breakdown in long gaps at high pd is characterized by

    1. Apurely uniform Townsend only at all gaps
    2. Bno ionization whatsoever
    3. Cbreakdown independent of electrode geometry
    4. Dleader/streamer development bridging the gap rapidly
    💡 Explanation:

    Non-uniform fields favour streamer/corona progression to breakdown.

  4. Q4Past Paper · PPSC/FPSC/NTSmedium

    Dielectric breakdown in solids is often initiated by

    1. Aperfect homogeneous lattice only always
    2. Bzero electric field
    3. Cimpurities, voids or thermal hot spots under high stress
    4. Donly magnetic flux density
    💡 Explanation:

    Defects concentrate stress and trigger partial discharge and failure.

  5. Q5hard

    Liquid dielectric breakdown may involve

    1. Aonly electron avalanche in vacuum always
    2. Bbubble formation and electrohydrodynamic instability
    3. Cno role of impurities
    4. Dinfinite viscosity preventing motion
    💡 Explanation:

    Low dielectric strength regions and bubbles lower breakdown voltage.

  6. Q6Past Paper · PPSC/FPSC/NTSmedium

    Impulse breakdown voltage of an insulator is typically

    1. Aalways lower than DC breakdown
    2. Bhigher than power-frequency breakdown for short duration stresses
    3. Cequal to corona inception only
    4. Dzero for lightning
    💡 Explanation:

    Short impulses may not allow full breakdown development; strength depends on wave shape.

  7. Q7Past Paper · PPSC/FPSC/NTSeasy

    Withstand voltage test on HV equipment verifies

    1. Aonly contact resistance of terminals
    2. Bonly nameplate MVA
    3. Conly rotor inertia
    4. Dinsulation can endure specified test voltage without failure
    💡 Explanation:

    Withstand tests demonstrate dielectric integrity per standards.

  8. Q8Past Paper · PPSC/FPSC/NTSeasy

    Creepage and clearance distances on insulators prevent

    1. Aonly conductor heating
    2. Bflashover along surfaces and through air
    3. Conly skin effect
    4. Donly transformer magnetizing current
    💡 Explanation:

    Adequate spacing avoids breakdown paths under operating and surge voltages.

  9. Q9Past Paper · PPSC/FPSC/NTSmedium

    Breakdown strength of air at atmospheric pressure in uniform field is approximately

    1. A30 kV/cm order of magnitude
    2. B1 V/cm
    3. C1000 kV/cm always
    4. Dindependent of gap
    💡 Explanation:

    Roughly 3 MV/m for uniform air gaps near STP.

  10. Q10hard

    Vacuum breakdown at very small gaps can be worsened by

    1. Aonly high humidity of air
    2. Bonly oil viscosity
    3. Conly cable capacitance
    4. Dmicroparticles and field emission at electrode surfaces
    💡 Explanation:

    Particle-induced breakdown and protrusions limit vacuum hold-off.

  11. Q11Past Paper · PPSC/FPSC/NTSmedium

    Thermal breakdown in solid cable insulation occurs when

    1. Adielectric losses cause heating exceeding heat removal capability
    2. Bonly at zero voltage
    3. Conly during DC corona
    4. Donly in vacuum gaps
    💡 Explanation:

    Loss heating can run away if insulation temperature exceeds limit.

  12. Q12medium

    Electrode conditioning and humidity can

    1. Anever affect results
    2. Bfix Paschen minimum to zero
    3. Csignificantly alter measured breakdown voltage in laboratory gaps
    4. Deliminate need for standards
    💡 Explanation:

    Surface state and gas humidity influence reproducibility of breakdown tests.

  13. Q13Past Paper · PPSC/FPSC/NTSeasy

    Corona discharge in HV systems is

    1. Afull insulation puncture through solid dielectric
    2. Bpartial ionization of air near conductors where local field exceeds ionization threshold
    3. Conly DC motor commutation sparking
    4. Donly transformer copper loss
    💡 Explanation:

    Corona is localized glow/brush discharge without complete flashover.

  14. Q14Past Paper · PPSC/FPSC/NTSmedium

    Corona onset on a smooth conductor in air is related to

    1. Asurface voltage gradient exceeding corona inception threshold
    2. Bonly conductor length in km
    3. Conly power factor of load
    4. Donly frequency below 1 Hz only
    💡 Explanation:

    High E-field at conductor surface initiates ionization in surrounding air.

  15. Q15easy

    Visual corona on HV lines is more noticeable

    1. Aonly in dry desert at noon exclusively
    2. Bonly inside oil-filled transformers visibly
    3. Cduring wet or foggy conditions and at night
    4. Donly at zero voltage
    💡 Explanation:

    Moisture and darkness aid observation of corona glow and hissing.

  16. Q16Past Paper · PPSC/FPSC/NTSmedium

    Corona power loss on transmission lines

    1. Ais always zero on EHV lines
    2. Bincreases with voltage above corona inception and with conductor surface conditions
    3. Cdecreases as voltage rises without limit
    4. Ddepends only on tower height
    💡 Explanation:

    Corona losses add to I²R loss and audible noise.

  17. Q17Past Paper · PPSC/FPSC/NTSeasy

    Bundled conductors on EHV lines reduce corona by

    1. Aincreasing surface gradient
    2. Bincreasing effective radius and lowering surface voltage gradient
    3. Cremoving all electric field
    4. Dusing only DC without any AC
    💡 Explanation:

    Multiple sub-conductors reduce peak E-field at given line voltage.

  18. Q18Past Paper · PPSC/FPSC/NTSeasy

    Corona produces

    1. Aonly useful heating of load
    2. Bonly negative resistance in cables
    3. Conly improved power factor always
    4. Dozone, audible noise, light emission and power loss
    💡 Explanation:

    Ionization side effects include chemical and acoustic emissions.

  19. Q19medium

    Radio interference (RI) from corona on HV lines is mitigated by

    1. Aincreasing sharp edges on conductors
    2. Bremoving earth wire
    3. Csmooth conductor surfaces, bundled conductors and optimized line design
    4. Doperating at DC zero only
    💡 Explanation:

    Surface irregularities intensify corona and RI.

  20. Q20hard

    Positive and negative corona differ in that

    1. Apositive corona is often more continuous while negative may be patchy (Trichel pulses)
    2. Bthey are identical in all conditions
    3. Conly negative exists in AC
    4. Donly positive exists in vacuum
    💡 Explanation:

    Polarity affects space charge and discharge morphology.

  21. Q21Past Paper · PPSC/FPSC/NTSmedium

    Corona ring (grading ring) on hardware reduces corona at

    1. Atransformer core laminations only
    2. Bconductor fittings, clamps and sharp edges
    3. Cmotor rotor bars only
    4. Dbattery terminals only
    💡 Explanation:

    Grading rings spread field and lower local stress concentrations.

  22. Q22hard

    Fair weather corona loss estimation uses

    1. Aonly transformer OC test data
    2. Bonly cable Murray loop
    3. Conly PID tuning constants
    4. Dempirical formulas based on conductor size, voltage and weather
    💡 Explanation:

    Peterson, Peek and similar relations estimate fair-weather corona loss.

  23. Q23Past Paper · PPSC/FPSC/NTSmedium

    Under foul weather, corona and flashover risk

    1. Adecreases to zero always
    2. Bis unrelated to pollution
    3. Cincreases due to water films and contamination on insulators
    4. Deliminates need for creepage
    💡 Explanation:

    Wet polluted surfaces provide conductive paths lowering flashover voltage.

  24. Q24hard

    DC corona on HVDC lines differs from AC because

    1. ADC has no electric field
    2. Bspace charge accumulates with one polarity affecting field distribution
    3. CAC has no corona ever
    4. DDC eliminates ionization
    💡 Explanation:

    Unipolar ion flow modifies ambient field along HVDC corridors.

  25. Q25Past Paper · PPSC/FPSC/NTSeasy

    Corona inception voltage can be raised by

    1. Apolishing conductor surface and increasing conductor diameter
    2. Badding sharp points to conductors
    3. Creducing clearance to ground
    4. Dusing thinner single small conductor at same voltage
    💡 Explanation:

    Smoother, larger radius lowers maximum surface gradient.

  26. Q26Past Paper · PPSC/FPSC/NTSeasy

    Insulation coordination ensures

    1. Aequipment insulation levels are matched to expected overvoltages and protective devices
    2. Bzero need for surge arresters
    3. Cidentical BIL for all equipment regardless of role
    4. Donly mechanical strength of towers
    💡 Explanation:

    Coordination balances cost and reliability against switching, lightning and temporary overvoltages.

  27. Q27Past Paper · PPSC/FPSC/NTSeasy

    Basic Insulation Level (BIL) of equipment refers to

    1. Acontinuous RMS voltage only
    2. Bshort-circuit MVA only
    3. Cspecified impulse withstand voltage capability
    4. Dno-load current only
    💡 Explanation:

    BIL defines standard lightning impulse withstand strength.

  28. Q28Past Paper · PPSC/FPSC/NTSmedium

    Metal-oxide surge arrester (MOA) protects equipment by

    1. Aincreasing fault current intentionally
    2. Bopening series breakers only
    3. Cclamping overvoltages and diverting surge current to earth
    4. Draising BIL of transformers permanently
    💡 Explanation:

    Arresters limit voltage across protected insulation during surges.

  29. Q29Past Paper · PPSC/FPSC/NTSmedium

    Protective margin in insulation coordination is

    1. Aalways zero by definition
    2. Bdifference between equipment withstand and protective level of arrester
    3. Cequal to line length only
    4. Dsame as power factor
    💡 Explanation:

    Adequate margin ensures arrester operates before insulation fails.

  30. Q30Past Paper · PPSC/FPSC/NTShard

    Switching surge is significant for insulation coordination on

    1. Aonly 11 kV distribution
    2. BEHV and UHV systems above about 300 kV
    3. Conly DC control circuits
    4. Donly motor starter panels
    💡 Explanation:

    Switching overvoltages dominate over lightning for very high voltage systems.

  31. Q31hard

    CFO (critical flashover) voltage of an insulator string is used in

    1. Astatistical insulation coordination studies
    2. Bonly DC resistance measurement
    3. Conly motor slip calculation
    4. Donly cable ampacity tables
    💡 Explanation:

    CFO distributions model probability of flashover under overvoltage.

  32. Q32Past Paper · PPSC/FPSC/NTSmedium

    Temporary overvoltage (TOV) following fault or load rejection can

    1. Astress arrester and insulation if not coordinated
    2. Bnever occur on transmission lines
    3. Conly affect LV fuses
    4. Deliminate Ferranti rise
    💡 Explanation:

    TOV duration and magnitude affect arrester energy duty.

  33. Q33Past Paper · PPSC/FPSC/NTSmedium

    Shielding angle and earth wire design on transmission lines improve

    1. Aonly corona loss without shielding effect
    2. Bonly cable charging current
    3. Clightning protection by reducing strikes to phase conductors
    4. Donly transformer impedance
    💡 Explanation:

    Effective shielding intercepts direct strokes to conductors.

  34. Q34Past Paper · PPSC/FPSC/NTSmedium

    Standard lightning impulse test wave shape is commonly

    1. ADC ramp only
    2. B50 Hz sine only
    3. Csquare wave of 1 ms only
    4. D1.2/50 μs voltage wave
    💡 Explanation:

    1.2 μs front and 50 μs tail define the standard impulse.

  35. Q35Past Paper · PPSC/FPSC/NTSeasy

    Pollution level of an installation site affects

    1. Arequired creepage distance of outdoor insulators
    2. Bonly conductor ampacity
    3. Conly rotor resistance
    4. Donly battery capacity
    💡 Explanation:

    Higher contamination needs longer creepage for same withstand.

  36. Q36hard

    Coordination between arrester rating and transformer insulation considers

    1. Amaximum continuous operating voltage and temporary overvoltages
    2. Bonly no-load loss
    3. Conly motor starting current
    4. Donly cable burial depth
    💡 Explanation:

    MCOV and TOV capability must align with system earthing and faults.

  37. Q37Past Paper · PPSC/FPSC/NTSmedium

    Silhouette factor and specific creepage distance (SCD) are used to select

    1. Aonly underground cable size
    2. Binsulator profiles for polluted environments
    3. Conly VFD carrier frequency
    4. Donly train pantograph pressure
    💡 Explanation:

    SCD (mm/kV) guides pollution-specific insulator design.

  38. Q38Past Paper · PPSC/FPSC/NTSeasy

    High-voltage AC test transformers are used to

    1. Aonly measure earth resistance
    2. Bonly start induction motors
    3. Cproduce test voltages for dielectric withstand and partial discharge tests
    4. Donly regulate turbine governors
    💡 Explanation:

    Test sets generate controlled HV for factory and field tests.

  39. Q39Past Paper · PPSC/FPSC/NTSmedium

    Partial discharge (PD) measurement detects

    1. Aonly copper losses in windings
    2. Bonly rotor speed deviation
    3. Clocalized dielectric stress that may precede insulation failure
    4. Donly solar irradiance
    💡 Explanation:

    PD pulses indicate voids, cracks or contamination in insulation.

  40. Q40Past Paper · PPSC/FPSC/NTSmedium

    Tan delta (dielectric loss angle) test on insulation indicates

    1. Aonly conductor cross-section
    2. Bdielectric quality and moisture or ageing
    3. Conly gearbox ratio
    4. Donly wind cut-in speed
    💡 Explanation:

    Elevated tan δ suggests deteriorated or wet insulation.

  41. Q41hard

    Impulse generator Marx circuit produces

    1. Aonly DC ripple free voltage
    2. Bhigh lightning or switching impulse voltages for testing
    3. Conly 50 Hz unregulated supply
    4. Donly biogas pressure
    💡 Explanation:

    Marx stages multiply charging voltage to impulse peak.

  42. Q42medium

    Sphere gap is used in HV laboratories to

    1. Ameasure only current transformer ratio
    2. Bcalibrate only watt-hour meters
    3. Cmeasure peak voltage by calibrated breakdown spacing
    4. Dtest only soil pH
    💡 Explanation:

    Standard sphere gaps give reproducible breakdown vs spacing.

  43. Q43Past Paper · PPSC/FPSC/NTSeasy

    SF6 gas in HV switchgear and GIS provides

    1. Alower dielectric strength than air at same pressure
    2. Bonly lubrication of contacts
    3. Conly cooling of solar panels
    4. Dhigh dielectric strength and arc quenching capability
    💡 Explanation:

    SF6 has excellent insulation and arc extinction properties in enclosed gear.

  44. Q44Past Paper · PPSC/FPSC/NTSmedium

    Vacuum interrupter in HV breakers extinguishes arc by

    1. Aoil blast only
    2. Bair at atmospheric pressure only
    3. Cwater jet only
    4. Drapid reduction of plasma in high vacuum with metal vapour condensation
    💡 Explanation:

    Vacuum bottles have low dielectric recovery and are common in MV/HV vacuum breakers.

  45. Q45medium

    Capacitance voltage divider (CVD) is used for

    1. Ameasuring high voltages by ratio of capacitors
    2. Bstarting synchronous motors only
    3. Cbiogas methane measurement only
    4. Dyaw control of wind turbines only
    💡 Explanation:

    CVD scales down HV for instrumentation safely.

  46. Q46hard

    Field intensity on an HV bushing is controlled by

    1. Asingle uniform paper layer only
    2. Bremoving all capacitive grading
    3. Cusing only air gaps internally
    4. Dgraded insulation and condenser layers
    💡 Explanation:

    Condenser bushings grade axial stress along the insulator.

  47. Q47Past Paper · PPSC/FPSC/NTSeasy

    Routine tests on HV transformers include

    1. Aonly blade pitch angle
    2. Bonly train braking distance
    3. Cmeasurement of ratio, polarity, winding resistance and insulation resistance
    4. Donly MPPT algorithm code
    💡 Explanation:

    Factory routine tests verify assembly before type/special tests.

  48. Q48medium

    Type tests on HV equipment demonstrate

    1. Aonly paint colour compliance
    2. Bonly nameplate font size
    3. Conly shipping weight
    4. Ddesign meets standard requirements including dielectric and thermal limits
    💡 Explanation:

    Type tests are destructive or severe and validate design class.

  49. Q49Past Paper · PPSC/FPSC/NTSeasy

    Earthing of HV test areas and labs is critical to

    1. Aincrease corona on purpose
    2. Beliminate all insulation
    3. Cmeasure only solar Voc
    4. Dpersonnel safety and correct fault current paths during tests
    💡 Explanation:

    Proper ground grids limit step/touch potentials during HV work.