Earthing, Safety and Pakistan Grid Practices MCQs 2026

50 questions with detailed answers · 38 from past papers · 5 quiz batches available

📚 Electrical Engineering📄 38 Past-Paper Qs✓ Free · No Login Needed
🎯 Mock Test

Read each question, think about the answer, then click Show Answer to reveal the correct option and explanation. Load 10 at a time so it stays manageable — perfect for one-topic study sessions on the bus or during a break.

Page 1 of 1Questions 1–10 of 50
  1. Q1Past Paper · PPSC/FPSC/NTSmedium

    Safety tagging on isolated NTDC circuits uses

    1. Agreen tag meaning energize
    2. Bno documentation
    3. Ctags on unrelated feeders only
    4. Ddanger tags and earth tags after proven dead and earthed
    💡 Explanation:

    Tag system communicates status to all personnel.

  2. Q2Past Paper · PPSC/FPSC/NTSeasy

    Grid frequency in Pakistan is nominally

    1. A60 Hz always without exception
    2. B25 Hz for all transmission
    3. C400 Hz for distribution
    4. D50 Hz with operational limits per grid code
    💡 Explanation:

    Synchronized area operates at 50 Hz like much of Asia/Europe.

  3. Q3Past Paper · PPSC/FPSC/NTSeasy

    Working near exposed busbars in substation requires

    1. Aconductive jewelry for convenience
    2. Bwet cotton gloves only
    3. Carc-rated clothing and insulated tools per hazard assessment
    4. Dno barricades ever
    💡 Explanation:

    EHV environments demand rigorous PPE and procedure.

  4. Q4Past Paper · PPSC/FPSC/NTSeasy

    Consumer earthing inspection under distribution safety rules checks

    1. Aonly decorative wiring
    2. Bonly highest lamp wattage
    3. Conly motor paint color
    4. Dearth electrode resistance, bonding and RCD operation
    💡 Explanation:

    DISCOs enforce safe installation practices at service.

  5. Q5medium

    Reporting of major grid disturbances to regulator supports

    1. Areliability monitoring and corrective investment under NEPRA framework
    2. Bonly internal memo without data
    3. Cdeletion of event records
    4. Dno protection review
    💡 Explanation:

    Performance standards drive accountability.

  6. Q6medium

    Live-line maintenance on transmission requires

    1. Aany worker without PPE
    2. Bshorting phase to earth without permit
    3. Cignoring weather limits always
    4. Dtrained crews, approved tools and safety distances per utility procedure
    💡 Explanation:

    Hot-line work follows strict NTDC safety manuals.

  7. Q7Past Paper · PPSC/FPSC/NTShard

    Neutral earthing in transmission is often through

    1. Afloating without any monitoring
    2. Bdirect connection to street lighting circuit
    3. Conly ELCB at 30 mA on EHV bus
    4. Dsubstation transformer neutral reactor/resistor or solid ground per study
    💡 Explanation:

    Grounding practice limits fault current and overvoltages.

  8. Q8Past Paper · PPSC/FPSC/NTSmedium

    Distributed generator connecting to grid must meet NEPRA/NTDC requirements for

    1. Auncontrolled energization during outage
    2. Bno circuit breaker at POI
    3. Canti-islanding, protection, metering and power quality
    4. Dreverse power flow without study
    💡 Explanation:

    Interconnection standards protect grid and personnel.

  9. Q9hard

    Incident energy study for NTDC/DISCO switchgear supports

    1. Aonly lamp maintenance factor
    2. Bselection of arc-flash PPE and safe working distances
    3. Conly motor slip calculation
    4. Donly cable charging MVAR
    💡 Explanation:

    Arc flash hazard analysis protects maintenance staff.

  10. Q10Past Paper · PPSC/FPSC/NTShard

    Earthing of NTDC substation structures and equipment follows

    1. Aonly single 1 ohm rod without study
    2. Bengineered earth grid design for fault current and touch/step limits
    3. Cfloating earth without reference
    4. Dconnection to phase conductor
    💡 Explanation:

    IEEE 80 / IEC practices model grid resistance and gradients.

  11. Q11Past Paper · PPSC/FPSC/NTSmedium

    Protection coordination on NTDC grid ensures

    1. Aall breakers trip on any fault simultaneously always
    2. Bno relay settings ever changed
    3. Cfault cleared by nearest breaker with backup discrimination
    4. Donly fuse protection on 500 kV
    💡 Explanation:

    Time and distance grading maintain stability and supply.

  12. Q12Past Paper · PPSC/FPSC/NTSmedium

    Authorization to work on NTDC substation equipment requires

    1. Aonly verbal agreement
    2. Bdirect energization for test without lockout
    3. Cpermit-to-work and isolation with earth application procedures
    4. Dbypassing interlocks routinely
    💡 Explanation:

    Systematic LOTO prevents accidental re-energization.

  13. Q13Past Paper · PPSC/FPSC/NTSeasy

    Safety clearance from live overhead lines for workers is governed by

    1. Aonly luminaire spacing tables
    2. BNTDC/utility safety rules and IE Rules aligned practices
    3. Conly motor nameplate only
    4. Donly cable color mnemonic
    💡 Explanation:

    Approach distances depend on voltage level.

  14. Q14Past Paper · PPSC/FPSC/NTSmedium

    Permissible voltage variation at consumer terminals in many standards is approximately

    1. A±6% or as per applicable regulation
    2. B±50% without limit
    3. Cexactly 0% always
    4. D±30% for all loads
    💡 Explanation:

    Voltage quality clauses protect equipment and service quality.

  15. Q15Past Paper · PPSC/FPSC/NTSmedium

    Grid Code issued under NEPRA framework defines

    1. Atechnical and safety requirements for grid-connected parties
    2. Bonly color of insulators without electrical limits
    3. Conly welding electrode sizes
    4. Donly lamp CRI values
    💡 Explanation:

    Grid code sets voltage, fault ride-through, protection and metering rules.

  16. Q16Past Paper · PPSC/FPSC/NTSeasy

    NTDC operates

    1. Aonly domestic house wiring
    2. Bonly diesel generator retail sales
    3. Conly street lighting design
    4. Dnational transmission grid and bulk power dispatch in Pakistan
    💡 Explanation:

    National Transmission and Despatch Company manages EHV network.

  17. Q17Past Paper · PPSC/FPSC/NTSeasy

    NEPRA in Pakistan regulates

    1. Aonly telecommunications spectrum
    2. Bonly water supply tariffs
    3. Celectric power sector including licensing and consumer protection standards
    4. Donly aviation fuel pricing
    💡 Explanation:

    National Electric Power Regulatory Authority oversees electricity market.

  18. Q18Past Paper · PPSC/FPSC/NTSmedium

    Periodic inspection of RCD includes

    1. Atrip time test at rated residual current per IEC 61557
    2. Bonly painting enclosure
    3. Conly tightening lamp holder
    4. Donly measuring lux level
    💡 Explanation:

    Test equipment verifies trip within specified milliseconds.

  19. Q19hard

    Fire protection RCDs may be rated

    1. A300 mA with time delay for discrimination
    2. B30 mA on entire factory incomer without grading
    3. C3 A residual only
    4. Dwithout any earthing
    💡 Explanation:

    Higher threshold prevents nuisance trips on leakage capacitance.

  20. Q20Past Paper · PPSC/FPSC/NTSeasy

    RCD rated residual operating current IΔn is

    1. Athe load current rating In only
    2. Bthe leakage current at which the device must trip
    3. Cthe breaking capacity in kA only
    4. Dthe lamp lumen output
    💡 Explanation:

    IΔn (e.g., 30 mA, 100 mA, 300 mA) sets sensitivity class.

  21. Q21Past Paper · PPSC/FPSC/NTSmedium

    In TT installations RCD is often mandatory because

    1. Aearth resistance is always zero
    2. Bearth fault loop impedance may be too high for fast MCB disconnection
    3. Cneutral is solidly earthed at consumer
    4. Dno touch voltage can exist
    💡 Explanation:

    RCD clears faults at low leakage current without low Zs.

  22. Q22Past Paper · PPSC/FPSC/NTSmedium

    ELCB/RCD must be connected such that

    1. Aneutral bypasses sensor always
    2. Bearth wire carries load current intentionally
    3. Call live conductors pass through the toroidal sensor
    4. Dphase is left out of sensor
    💡 Explanation:

    Differential sensing requires all current-carrying wires through core.

  23. Q23hard

    Type AC RCD is suitable for

    1. Apure DC leakage only without AC component
    2. Bhigh-frequency PWM without Type A/B consideration
    3. Csinusoidal AC residual currents
    4. Donly lightning impulse without evaluation
    💡 Explanation:

    Type A/B/AEV address pulsating DC and HF applications.

  24. Q24Past Paper · PPSC/FPSC/NTShard

    30 mA RCD may not detect

    1. Aline-to-line fault if no earth path involved (unlikely on earthed systems)
    2. Bline-to-earth fault through person
    3. Cleakage via damaged cable to wet floor
    4. Dappliance frame fault to PE
    💡 Explanation:

    RCD needs earth leakage path; MCB clears line faults.

  25. Q25Past Paper · PPSC/FPSC/NTSmedium

    IEC 60439 / modern switchgear may use RCBO which combines

    1. Aovercurrent protection and residual current protection in one device
    2. Bonly lighting dimmer
    3. Conly surge arrester without MCB
    4. Donly ammeter shunt
    💡 Explanation:

    RCBO protects cable and persons on same pole.

  26. Q26easy

    RCD test button creates

    1. Apermanent short of phase to neutral for load
    2. Bsimulated imbalance to verify mechanical trip function
    3. Copen-circuit of earth electrode
    4. Dincrease of supply voltage to 440 V
    💡 Explanation:

    Monthly user test confirms trip mechanism operates.

  27. Q27hard

    Selective (time-graded) RCD coordination uses

    1. Aall 30 mA instant on main incomer only
    2. Bno earthing on sub-circuits
    3. Chigher sensitivity downstream and delayed upstream devices
    4. Donly fuse without any RCD
    💡 Explanation:

    Discrimination limits outage to faulted circuit.

  28. Q28Past Paper · PPSC/FPSC/NTSmedium

    RCD nuisance tripping may be caused by

    1. Aperfect insulation with zero leakage always
    2. Bunity power factor alone
    3. Ccorrect TN-S wiring only
    4. Dcumulative leakage from filters, capacitors and damp equipment
    💡 Explanation:

    Equipment capacitive leakage can approach 30 mA threshold.

  29. Q29medium

    Voltage-operated ELCB is largely superseded because

    1. Ait is always faster than 1 ms
    2. Bit depends on rise of earth voltage and may be less reliable
    3. Cit eliminates need for earthing
    4. Dit measures only DC traction current
    💡 Explanation:

    Current-balance RCD is preferred in modern installations.

  30. Q30Past Paper · PPSC/FPSC/NTSmedium

    RCD does not replace

    1. Aovercurrent protection (MCB/fuse) for short circuit and overload
    2. Bneed for earthing
    3. Cinsulation on conductors
    4. Dcorrect wiring polarity checks
    💡 Explanation:

    RCD handles leakage; MCB handles overcurrent.

  31. Q31Past Paper · PPSC/FPSC/NTSeasy

    Standard residential RCD sensitivity is often

    1. A300 A
    2. B30 A
    3. C30 mA for additional protection against shock
    4. D3 A
    💡 Explanation:

    30 mA limits shock duration/current for wet locations.

  32. Q32Past Paper · PPSC/FPSC/NTSeasy

    Residual Current Device (RCD) operates when

    1. Aload power factor is unity only
    2. Bvoltage is exactly 230 V
    3. Cmotor is underloaded
    4. Dvector sum of line currents deviates from zero (leakage to earth)
    💡 Explanation:

    Differential current through toroidal core trips device.

  33. Q33Past Paper · PPSC/FPSC/NTSeasy

    Earth Leakage Circuit Breaker (ELCB) detects

    1. Aonly overvoltage on lighting circuit
    2. Bimbalance indicating leakage current to earth
    3. Conly motor rpm
    4. Donly transformer flux density
    💡 Explanation:

    Core-balance or voltage-operated types sense earth leakage.

  34. Q34medium

    Minimum size of main earthing conductor in many codes depends on

    1. Aonly lamp wattage
    2. Blargest incoming service conductor and fault level
    3. Conly motor color code
    4. Donly cable brand name
    💡 Explanation:

    Cross-section must carry prospective earth fault current.

  35. Q35Past Paper · PPSC/FPSC/NTSmedium

    Lightning protection earth should be

    1. Aalways completely isolated without bonding rules
    2. Bconnected only to phase conductor
    3. Cbonded to power system earth where codes permit common electrode
    4. Dleft unconnected intentionally
    💡 Explanation:

    Coordinated bonding avoids dangerous potential differences.

  36. Q36Past Paper · PPSC/FPSC/NTShard

    Earth mat in substations is provided to

    1. Alimit step and touch potentials during grid faults
    2. Bincrease fault current path impedance only
    3. Cdecorate switchyard only
    4. Dreplace insulation coordination
    💡 Explanation:

    Buried or surface mesh equalizes potential under EHV equipment.

  37. Q37medium

    Chemical earthing (maintenance-free) uses

    1. Aonly dry sand without metal
    2. Bconductive compounds around electrode to lower contact resistance
    3. Conly insulating varnish on rod
    4. Donly neon lamp gas
    💡 Explanation:

    Hygroscopic compounds keep moisture around electrode.

  38. Q38Past Paper · PPSC/FPSC/NTShard

    Step potential hazard near earth electrode during fault is

    1. Avoltage across lamp filament only
    2. Bflux in transformer core only
    3. Cvoltage difference between feet at different soil potentials
    4. Dpower factor of motor only
    💡 Explanation:

    Gradient in earth potential can shock personnel nearby.

  39. Q39hard

    TN-C-S (PME) combines neutral and earth on supply side with

    1. Aseparate PE after split at consumer service
    2. Bpermanent combined PEN to all sockets without split
    3. Cno earthing at transformer
    4. Donly DC traction return
    💡 Explanation:

    PEN becomes separate N and PE at customer intake.

  40. Q40Past Paper · PPSC/FPSC/NTShard

    TT system earthing has

    1. Ano earth electrode at all
    2. Bphase and neutral shorted at load
    3. Conly IT system without any earth
    4. Dlocal earth electrode at consumer with utility neutral earthed separately
    💡 Explanation:

    TT relies on local R_A and RCD due to higher loop impedance.

  41. Q41Past Paper · PPSC/FPSC/NTSmedium

    Separate protective earth (PE) and neutral (N) must not be

    1. Acombined after the main earthing terminal except as defined by TN-S rules
    2. Bbonded at every socket always incorrectly
    3. Cleft floating on consumer side
    4. Dconnected only to phase
    💡 Explanation:

    TN-S keeps N and PE separate to avoid neutral current on earth paths.

  42. Q42medium

    Ring earth electrode around building in IEC practice provides

    1. Amore uniform earth potential and lower resistance
    2. Bhigher touch voltage always
    3. Cno connection to main earthing terminal
    4. Donly lightning without power earthing
    💡 Explanation:

    Ring in trench with electrodes improves contact area.

  43. Q43Past Paper · PPSC/FPSC/NTSmedium

    Measurement of earth resistance commonly uses

    1. Aonly voltmeter across open circuit
    2. Bfall-of-potential (three-point) method
    3. Conly wattmeter on lighting load
    4. Donly oscilloscope on communication line
    💡 Explanation:

    Auxiliary electrode placement determines measured earth R.

  44. Q44Past Paper · PPSC/FPSC/NTSmedium

    Soil resistivity affects earth electrode resistance such that

    1. Aresistivity has no effect
    2. Bdry rocky soil always gives lowest R
    3. Conly pipe length color matters
    4. Dhigher resistivity soil gives higher electrode resistance
    💡 Explanation:

    R_e ∝ ρ; measurement drives electrode design.

  45. Q45Past Paper · PPSC/FPSC/NTSeasy

    Earth continuity conductor (ECC) ensures

    1. Aphase voltage appears on casing
    2. Bmetallic enclosures remain at earth potential during faults
    3. Cneutral is never connected
    4. Dfuses never blow
    💡 Explanation:

    ECC links exposed conductive parts to main earth.

  46. Q46Past Paper · PPSC/FPSC/NTSmedium

    IS/IEC practice requires main equipotential bonding to connect

    1. Aonly lighting switches
    2. Bincoming metal services and structural metal to earth terminal
    3. Conly decorative paint
    4. Donly plastic pipes without metal
    💡 Explanation:

    Bonding limits potential differences during earth faults.

  47. Q47Past Paper · PPSC/FPSC/NTSeasy

    Plate earth electrode uses

    1. Aonly overhead conductor
    2. Bonly fluorescent lamp ballast
    3. Cburied metal plate (GI or copper) in a pit with alternating layers of coke and salt
    4. Donly transformer oil only
    💡 Explanation:

    Large plate area contacts soil to reduce resistance.

  48. Q48Past Paper · PPSC/FPSC/NTSeasy

    Pipe earth electrode is commonly made of

    1. APVC conduit only
    2. Bwooden pole only
    3. Cair gap only
    4. Dgalvanized iron or copper pipe driven vertically into soil
    💡 Explanation:

    Metal pipe in moist soil forms electrode; backfill with salt/coal may lower R.

  49. Q49Past Paper · PPSC/FPSC/NTSeasy

    Earth electrode resistance should generally be

    1. Aas high as possible
    2. Bequal to load resistance
    3. Cinfinite for safety
    4. Das low as practicable per national code (often ≤1–5 Ω for small installations)
    💡 Explanation:

    Lower resistance improves fault clearance and touch voltage control.

  50. Q50Past Paper · PPSC/FPSC/NTSeasy

    Purpose of electrical earthing in installations is primarily to

    1. Aprovide a low-impedance path for fault current and limit touch voltage
    2. Bincrease line voltage for efficiency
    3. Celiminate need for overcurrent protection
    4. Dstore energy in soil
    💡 Explanation:

    Earthing enables protective devices to operate and reduces shock risk.